Customer Support: 07031622093
Profile: Tower
Rating: 1kVA - 10kVA
Voltage: 220/230Vac
Frequency: 50Hz
Input | |
Voltage | 230 Vac |
Tolerance | Normal Over-voltage: +10% |
Withstand Over-voltage: +15% (20% max limit) | |
Normal Under-voltage: - 20% | |
Withstand Low-voltage: - 30% (-37% lowest limit) | |
Power Factor | 0.98 |
Output | |
Voltage | 230Vac ± 1% |
Power Factor | FS Model: 0.8 |
FS-V Model: 0.9 | |
Transfer Time | 0 ms |
Frequency | 46 - 54Hz (On Mains) |
50Hz (On Battery) | |
Waveform | Pure Sine Wave |
THDi | Linear Load ≤ 3%; Non-linear Load ≤ 6% |
Crest Factor | 3 : 1 |
Bypass Facility | FS Model: Static Bypass |
FS-V Model: Both Maintenance Bypass and Static Bypass | |
DC Bus / DC Functions: | |
1kVA | 36V |
2kVA | 72/96V |
3kVA | 96V |
6/10kVA | 192V / 240V |
Cold-Start Function | Yes |
Charging Time | 6hr to recover to 90% capacity |
Battery Charging in OFF Mode | Yes |
Battery Type | Sealed, Maintenance-free VRLA |
LCD User Interface: | |
Metering / Indications for | Voltage |
Load % | |
Frequency | |
General Status | |
Alarm | |
Communication: | |
Interfaces | RS232, USB*, SNMP* (* Option) |
Overload | |
100~110% | Output swithes to bypass after 60s |
125~130% | Output swithes to bypass after 30s |
>130% | Output swithes to bypass after 100ms |
Environment: | |
Temperature | 0 ~ 40oC |
Humidity | 20 ~ 90% Non-condensing |
Noise Level | < 50dB from 1m |
IP Class | 20 |
Physical: | |
Dimensions (mm) | 1kVA : 145 x 405 x 220 (W x D x H) |
2-3kVA : 192 x 460 x 340 (W x D x H) | |
6-10kVA : 248 x 500 x 460 (W x D x H) | |
Weight (Kg) | 1kVA : 14kg |
2kVA : 34kg | |
3kVA : 34.5kg | |
6kVA : 57kg / 192V: 90kg / 240V | |
10kVA : 60kg / 192V; 93kg / 240V |
Profile: Tower Configuration | |
Range: 1kVA to 10kVA | |
Operation: Double-conversion Online | |
Active Power Factor Correction (0.98 input P.F) | |
Off-mode Charging | |
Cold Start Function | |
High Power Density | |
18 Months warranty (excluding battery) | |
Excellent support | |
Protection against accidental power ON / OFF | |
Input overload protection | |
LCD Interface: Voltage, load level, battery level, mains fail alarm, low battery, fault type, etc |
Powerex Limited warrants Vectronic® products to be free from defects in materials and workmanship under the conditions of normal use. The warranty period for each product range is as stated below. Powerex Limited guarantees the proper operation of Vectronic® products when used in accordance with the operating manual and within the limits of performance specifications.
Duration of Warranty
This warranty applies to the following Vectronic® product models respectively, for all distributors and end users, valid from the purchase date duly evidenced by invoice or receipt, for all products sourced through authorized or proper channels:
Limitations of Warranty
Below are designated Warranty Centres
63, Kudirat Abiola Way, Oregun
Ikeja, Lagos Nigeria
E-mail: support@melange-technology.com
932A Folashade Abike Street, Omole Phase II
Lagos Nigeria
E-mail: support@powerex-limited.com
Limitations and Exclusions
Optional Warranty Terms
No Ratings and Reviews Yet